Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0223-02909
Parcel: 136412660

Address:
10234 E EMILY PL

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0223-02909
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/03/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/03/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0223-02909 (10234 E EMILY PL TUCSON, AZ 85730)

DWG Page: P9 shows a total of 108.94A. The load calculation cannot exceed 100A for a 100A main breaker. Either the main breaker needs to increase for the load, or the panel needs upgrading. 2018 IRC E3602. Or provide a Supply side tap as given in 2017 NEC 705.12 for point of connection requirements.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
03/04/2023 PDSD Application Completeness Express REVIEW COMPLETED