Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-0223-02909
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/03/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/03/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0223-02909 (10234 E EMILY PL TUCSON, AZ 85730) DWG Page: P9 shows a total of 108.94A. The load calculation cannot exceed 100A for a 100A main breaker. Either the main breaker needs to increase for the load, or the panel needs upgrading. 2018 IRC E3602. Or provide a Supply side tap as given in 2017 NEC 705.12 for point of connection requirements. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 03/04/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |