Permit Number: TC-RES-0223-02734
Parcel: 116161590

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.2

Permit Number - TC-RES-0223-02734
Review Name: RESIDENTIAL NEW DWELLING v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/11/2024 Residential Building REQUIRES RESUBMIT TC-RES-0223-02734
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:

Clarify if the casita is a sleeping quarters (without kitchen) or an Accessory Dwelling Unit (ADU) which requires many alterations for compliance. The first submitted plan set did not have a kitchen in the casita. An ADU requires separate permit with a submittal filed under a new address.

Each dwelling unit with kitchen requires a separate Pima County assigned street address after Zoning approval, R319. https://www.pima.gov/1010/Addressing-Frequently-Asked-Questions

An impact fee payment is required for an ADU at the time of permit payment.

Show compliance with the Inclusive Home Design Ordinance adopted by the City of Tucson Ordinance #10463 on 10/16/2007. Notate accessible route, minimum door width, changes in floor elevation, door hardware, electrical outlet reach range, grab bar reinforcement, etc.

SITE PLAN:

1. Update the building square footage sizes with exterior foundation dimensions. Include each carport and patio cover.

PLANS:

1. Notate a cool (white) roof finish as required by the ADU provisions.
2. Show a maximum ½” floor elevation changes at a notated accessible route entrance on the floor plans for each dwelling, R106.1.1. Include all threshold conditions for a route from the exterior into the living space.
3. Provide a complete roof framing plan with beams and rafters sized with appropriate prescriptive load carrying capacity for the carport, R301.1.

SECTIONS - DETAILS:

1. Clarify the placement of ceiling/roof insulation for R806 compliance. Remove detail #3/A104.

PLUMBING PLANS:

1. Tucson Water Department limits flow rates for each water meter size in compliance with P2903.7. Show an appropriate meter size.

MECHANICAL PLANS:

1. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation with controlled exhaust, R303.4; N1103.6 & M1505.4. Show the minimum airflow rate setting and location of the device requiring this adjustable setting. A two or three bedroom dwelling under 1501 SF requires a 45 CFM continuous setting. A one bedroom dwelling under 1501 SF requires a 30 CFM continuous setting.
2. Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D.

ELECTRICAL PLANS:

1. Clarify if existing notation for a newly developed property.
2. Update the Riser Diagram showing a 200 AMP feeder size if providing a 200 AMP subpanel, NEC 225.30 and E3403.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits. Show full cutoff fixtures were located within 25 feet from the property line OLC 401.3.3.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/pdsd
04/04/2024 Site Zoning REQUIRES RESUBMIT Zoning has no issues with the proposed project. Please clarify if this permit is to be for Unit 1 or Unit 2. A permit for each unit will be required.

Nathan.Herrera@tucsonaz.gov.
02/29/2024 PDSD Application Completeness Express REVIEW COMPLETED