Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING v.2
Permit Number - TC-RES-0223-02636
Review Name: RESIDENTIAL NEW DWELLING v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/23/2023 | Site Zoning | APPROVED | |||
| 03/23/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/20/2023 | Residential Building | REQUIRES RESUBMIT | TC-RES-0223-02636 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet Zoning and other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans. Provide a clear and concise construction plan set. Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits FLOOR PLANS: 1. Provide a floor plan the proposed bathroom layout, R106.1.1. Fixtures require compliant spacing, Figure R307.1. PLUMBING PLANS: 1. Clarify the pipe diameter at the point of connection of the new cold water line to existing service pipes. Existing water pipes may require replacement with larger sizes for controlling excessive water flow rates, P2903.7. A minimum 3/4” pipe is required for supplying water to the new bathroom group fixtures. 2. Show an individual vent diameter not less than one-half the required drain diameter, but not less than 1-1/4”, P3113. MECHANICAL PLANS: 1. Show bathroom window size or an exhaust fan location with minimum 50 CFM rating and duct to the exterior, R303.3 and M1505. ELECTRICAL PLANS: 1. Show a receptacle outlet within 3’ of each lavatory basin in each bathroom, E3901.6. Show Bathroom receptacles with a separate 20 AMP dedicated circuit, E3703.4 and E3901.6. 2. Show a wall switch controlled light in the bathroom, E3903.3. If you have any questions, please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review Submit a corrected plan set at https://www.tucsonaz.gov/pdsd |