Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING v.1
Permit Number - TC-RES-0223-02581
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/02/2024 | Site Zoning | APPROVED | |||
| 01/24/2024 | Site Engineering | NOT REQUIRED | |||
| 01/24/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/04/2024 | Residential Building | REQUIRES RESUBMIT | TC-RES-0223-02581 R1 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes. The plans require sufficient detail for demonstrating an awareness of minimum building code compliance for passing all progress inspections. SITE PLAN: 1. Identify existing utility lines requiring alteration, R106.1.1. Show the location of the electrical service panel. 2. Show the location of the proposed water line connection to a minimum ¾” supply connection. 3. Show the location of the proposed sewer connection. FLOOR PLAN: 1. Show window sizes with type identified as fixed, XO or SH. SECTIONS - DETAILS: 1. Replace the removed container footing from sheet S-1.0, R106.1. 2. Show a complete cross-section detail of the new exterior wall, R106.1.1. Show the minimum 12” deep, continuous #4 rebar reinforced footing #1/S1.0, R403.1. 3. Show wall insulation between the conditioned space and Conex storage, N1101. 4. Clarify the placement of ceiling/roof insulation, R806. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing and tightly applied (minimum) R-30 insulation, R806.5. A single layer of batt insulation does not provide the required condensation control. Air space between roof sheathing and ceiling insulation requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2. PLUMBING PLANS: 1. Tucson Water Department limits flow rates for each water meter size in compliance with P2903.7. Show an appropriate yard pipe for supporting the existing and proposed dwelling units. 2. Show an individual accessible water supply shut off and water heater for the proposed building, P2903.9.1. MECHANICAL PLANS: 1. Show the heating capacity of the Blueridge unit, R303.9. ELECTRICAL PLANS: 1. Provide notation or a detail for protecting branch conductors between Panel C and the living space, E3802.3. If you have any questions, please contact: PDSD-Residential@tucsonaz.gov City of Tucson Residential Plan Review Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services |
||
| 12/28/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |