Permit Number: TC-RES-0223-02559
Parcel: 135083410

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0223-02559
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/22/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/06/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-RES-0223-02559

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
DENIED
1. The structural certification letter indicates that modifications to the existing framing are required, but required modifications are not spelled out in the letter. Modification appears to be doubling of each 2x8 rafter, resulting in passing scores. Revise the structural letter to specifically state the structural modifications required.
2. No structural modifications are shown on the submitted plan set. Revise the plan set to show the required structural modifications indicated in the revised certification letter.


BUILDING REVIEW COMMENTS:
DENIED
Resubmit revised plans showing structural revisions.


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
DENIED
Resubmit with revised plans showing structural revisions.

PLUMBING REVIEW COMMENTS:
N/A


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
02/22/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0223-02559

STRUCTURAL REVIEW COMMENTS: DENIED
1. The structural certification letter indicates that modifications to the existing framing are required, but required modifications are not spelled out in the letter. Modification appears to be doubling of each 2x8 rafter, resulting in passing scores. Revise the structural letter to specifically state the structural modifications required.
2. No structural modifications are shown on the submitted plan set. Revise the plan set to show the required structural modifications indicated in the revised certification letter.

ELECTRICAL REVIEW
1. AC Overcurrent Protective Device and Conductor Sizing for PV source Circuits and Module Interconnection Conductors (Imax x 1.25) Reference NEC 690.8(A)(3) and (B)(1). Show a complete calculation for determining OCPD and conductor requirements.
2. Maximum conductor ampacity is determined by applying correction and adjustment factors for temperature of insulation rating of 90C and CCC proximity. Reference NEC 310.15, Table 310.15(B)(2)(a), 310.15(B)(2)(b) and 310.15(B)(3)(a). The adjusted conductor rating may not be less than the calculated Conductor Sizing. Show a complete calculation for determining conductor sizing.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
02/03/2023 PDSD Application Completeness Express REVIEW COMPLETED