Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-RES-0126-00504
Parcel: 11108241A

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0126-00504
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/02/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/02/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT 2023 NEC 230.67 mandates whole-house surge protection (SPD) for services supplying dwelling units, dormitories, hotel/motel guest rooms, and patient rooms in nursing homes, requiring a Type 1 or Type 2 SPD, often built-in or next to the service, with a minimum 10kA nominal discharge current rating, and also applies to service replacement. Please re submit with plans reflecting Whole house surge protection.
02/02/2026 PDSD Application Completeness Express REVIEW COMPLETED