Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0126-00504
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/02/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/02/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | 2023 NEC 230.67 mandates whole-house surge protection (SPD) for services supplying dwelling units, dormitories, hotel/motel guest rooms, and patient rooms in nursing homes, requiring a Type 1 or Type 2 SPD, often built-in or next to the service, with a minimum 10kA nominal discharge current rating, and also applies to service replacement. Please re submit with plans reflecting Whole house surge protection. | ||
| 02/02/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |