Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0126-00215
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/16/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/16/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | Requires resubmit. Please note the following: 1. Provide a riser diagram to show the connection or feed to the existing service panel from new 400A panel service. Additionally, if using existing panel and converting to a subpanel, the main bonding jumper will need to be removed. 2. Provide additional information on wall that has pole 3. Show the location of the existing panel on the Electrical Plan and indicate if it will be a junction point for existing circuits or a sub-panel with new feeder conductors |
||
| 01/15/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |