Permit Number: TC-RES-0126-00207
Parcel: 113031030

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.2

Permit Number - TC-RES-0126-00207
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/16/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/16/2026 Addressing Validation REQUIRES RESUBMIT If you have questions regarding the Addressing Validation Review, please contact building_official@tucsonaz.gov. Parcel/addressing issue. The site plan shows to be for a triplex. This location does not have the three addresses attached. Please contact Pima County Addressing at addressing@pima.gov or 520-724-9512 to verify and add the addresses. After addresses have been added or verified, you'll need to submit an address change request to update this record in the sub records tab of the permit along with a new aerial/site plan that shows the corrected addressing.
01/16/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT Requires resubmit. Please note the following:

1. Provide an electrical riser diagram, E3604, include breaker/fuse sizes for overcurrent protection of feeder. Notate the grounding and bonding method, E3607. Metallic gas lines must be bonded and not be used as the primary grounding method, E3608.
2. Show each meter and address associated with each meter.
3. Provide Emergency Service Disconnects and markings per E3601.8
4. Provide Service Surge Protection per E3606.5.

If you have any questions, please email me at jorge.ruiz@tucsonaz.gov

Jorge Ruiz
Building Plans Examiner
01/15/2026 PDSD Application Completeness Express REVIEW COMPLETED