Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL ADD/ALT v.1
Permit Number - TC-RES-0126-00149
Review Name: RESIDENTIAL ADD/ALT v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/26/2026 | Residential Zoning | APPROVED | |||
| 01/30/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/30/2026 | Residential Building - Standard | REQUIRES RESUBMIT | Please address the comments below and re submit. 1. Edit your legal document (Construction documents) to reflect the 2024 IRC, not the 2018. 2. Please provide whole-house surge protection (SPD) for services supplying dwelling units 2023 NEC 230.67 3. R310.3.1 Installation near cooking appliances. Smoke alarms shall be installed not less than 10 feet (3048 mm) horizontally from a permanently installed cooking appliance. |
||
| 01/16/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |