Permit Number: TC-RES-0126-00128
Parcel: 11606235C

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.3

Permit Number - TC-RES-0126-00128
Review Name: RESIDENTIAL SOLAR v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/12/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/12/2026 Light Residential Building Review (OIP) - Standard REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov

Please resubmit addressing the following comments:
1) Provide a disconnecting means for the Energy Storage System (ESS) to combiner, provide all relevant labels 706.15.
2) Verify the number of conductors in the plan set, PV to combiner count does not reflect the 9 conductors displayed on the 3-line diagram. Conductors must not exceed 40% conduit fill E3904.6, Table E3904.6(10)