Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.3
Permit Number - TC-RES-0126-00128
Review Name: RESIDENTIAL SOLAR v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/12/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/12/2026 | Light Residential Building Review (OIP) - Standard | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comments: 1) Provide a disconnecting means for the Energy Storage System (ESS) to combiner, provide all relevant labels 706.15. 2) Verify the number of conductors in the plan set, PV to combiner count does not reflect the 9 conductors displayed on the 3-line diagram. Conductors must not exceed 40% conduit fill E3904.6, Table E3904.6(10) |
||
| 03/10/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |