PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Facilitate a shorter back check time: provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2024 International Residential Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2024 IRC code compliance.

Provide a response letter on separate file with submitting the updated construction plan set.

Provide a clear and concise construction plan set. Sample drawings for Garage are available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits

SITE PLAN:

1. Combine the site plan into the construction plan set, R106.1.1. .

PLANS:

1. Show the material composition of the wall separating the garage and dwelling. This wall requires a fire rated product in compliance with R302.6 such as ½” gypsum board (garage side).
2. A doorway from a garage directly into a sleeping room is not permitted, R302.5.1.
3. Clarify if the wall separating the dwelling from the proposed garage has any window of door openings, R302.5.1. Any openings require fire rated covering.
4. Show any door from a garage to dwelling with a 20-minute fire rating (or 1-3/8” solid core) with self-closing and self-latching provision, R302.5.1.
5. Provide a Roof Framing Plan showing the location and size of beams, headers, and rafters for supporting live and dead structural loads, R804.

SECTIONS - DETAILS:

1 Show a cross-section detail of the proposed exterior wall, R106.1.1. Show 3/8” structural or ½” non-structural wall sheathing of the proposed exterior wall, R106.1.1.
2 Show a complete cross-section detail of the new exterior wall, R106.1.1. Show the minimum 12” x 12” continuous #4 rebar reinforced footing, R403.1. Show with dimensions the exterior wood siding, water-resistive barrier, insulation, interior sheathing, and pressure treated sill anchored with ½” x bolts providing 7” embedment. Show the wall assembly with a 6” clearance above the ground or 2” clearance above an exterior concrete surface, R317.1 item 5. A stem is usually required.
3 Enclose the window between garage and dwelling or enlarge the opening into for a door with a 20-minute fire rating (or 1-3/8” solid core) with self-closing and self-latching provision, R302.5.1. A door directly into a sleeping room is not permitted, R302.5.1.
4 Show garage opening narrow panels with fastening details using a prescriptive method at Figure R602.10.6.2, R602.10.6.3 or R602.10.6.4.
5 Identify all fasteners for wind loading compliance. Show roof (uplift resistance) fasteners (H2.5) with appropriate uplift capacity, R802.11 amended.

ELECTRICAL PLANS:

1. Garage Branch Circuit: a separate (dedicated) GFCI 20-amp branch circuit required for receptacles in an attached garage and detached garages with service, E3703.5. A receptacle is required at each vehicle bay not more than 5.5 feet above the floor, E3901.9. Additional receptacles are optional.
2. Show a wall switch controlled light at garage entrances, E3903.3.

If you have any questions, please contact: