Permit Number: TC-RES-0125-00545
Parcel: 133383070

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0125-00545
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/05/2025 Site Zoning - Standard APPROVED
03/07/2025 Site Engineering - Standard NOT REQUIRED
03/07/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/20/2025 Residential Building - Standard REQUIRES RESUBMIT Provide a response letter on separate file with the updated construction plan set.
The simplified prescribed energy values for glazing is U=0.40, skylights U=0.65, ceiling R=38 and framed walls R=13. Mass wall requirement is R=4 when 50% of insulation is exterior and R=6 when applied interior, N1102.1. Show a means of achieving the prescriptive values at each assembly on the plans or show overall compliance if using less than prescribed component values by providing a RES check calculation.
02/04/2025 PDSD Application Completeness Express REVIEW COMPLETED