01/28/2025 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT Permit Review TC-RES-0125-00514 (6819 E SCARLETT ST TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Modifications and additions to the gas line require that the existing system be enlarged to meet the total demand based on the new length and load, G2412.3, G2412.4.
2. Size the pipe based on the length from the meter to the farthest attached appliance and max total demand of all attached appliances using Table G2413.4(1) (Metallic Pipe), Table G2413.4(7) Polyethylene Plastic Pipe. Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1.
3. Provide pipe sizes sized per Table G2413.4(1). Multiple segments and branches are undersized. For the given length and appliance demands.