Permit Number: TC-RES-0125-00467
Parcel: 11709075B

Address:
1031 S MEYER AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0125-00467
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/24/2025 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT Permit Review TC-RES-0125-00467 (1031 S MEYER AV TUCSON, AZ 85701)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Provide a complete gas piping template showing the connection and length from the meter to all attached appliances or note that this is a dedicated line, G2401.1, R301.1:
2. Provide appliance demands for pipe size compliance verification, G2413.4.1.
3. Size the pipe based on the length from the meter to the farthest attached appliance and max total demand of all attached appliances using Table G2413.4(1) (Metallic Pipe), Table G2413.4(7) Polyethylene Plastic Pipe. Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
01/24/2025 PDSD Application Completeness Express REVIEW COMPLETED