Permit Number: TC-RES-0125-00329
Parcel: 11623080E

Address:
845 W 18TH ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0125-00329
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2025 Site Zoning - Standard APPROVED
03/03/2025 Site Engineering - Standard NOT REQUIRED
03/03/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/04/2025 Residential Building - Standard REQUIRES RESUBMIT Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation, R806. Attic space outside of the thermal barrier requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2 or an unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation at either the roof or ceiling and provide appropriate roof sheathing moisture control .
01/30/2025 PDSD Application Completeness Express REVIEW COMPLETED