Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING v.1
Permit Number - TC-RES-0125-00329
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/28/2025 | Site Zoning - Standard | APPROVED | |||
| 03/03/2025 | Site Engineering - Standard | NOT REQUIRED | |||
| 03/03/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/04/2025 | Residential Building - Standard | REQUIRES RESUBMIT | Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation, R806. Attic space outside of the thermal barrier requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2 or an unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation at either the roof or ceiling and provide appropriate roof sheathing moisture control . | ||
| 01/30/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |