Permit Number: TC-RES-0125-00316
Parcel: 11203373A

Address:
3524 N TREAT AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.4

Permit Number - TC-RES-0125-00316
Review Name: RESIDENTIAL SIMPLE REVIEW v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/24/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/24/2025 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT ACTIVITY NO. TC-RES-0125-00316
ADDRESS/PARCEL: (3524 N TREAT AV TUCSON, AZ 85716)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter.
COMMENTS:
1. Thank you for submitting your Manual J with the load calculations for the total square footage of 2123
a. However, you are proposing to install 2 separate units. The 3T Heat Pump that covers the 3 bedrooms and 2 bathrooms, and the 3 Zone Mini Split that covers the kitchen/dining room, living room, and guest suite. Submit a Manual J, one for the section of the house being covered by the heat pump, and another for the section being covered by the mini split.
b. Please submit the extended rating table for each unit. It should contain the manufacturer’s name, the model, and the capacity.
2. For the gas piping, please provide the location of the pipe supports on the roof. How frequent is the support spacing?
3. Is the 5 ft section of metal pipe being capped or is this going to the gas fireplace? Please label on drawing. If going to fireplace, please provide the Btu demand of the fireplace.
4. The tankless water heater is located in the house? If it is, can you provide the exact location? The water heater will need proper exhaust and fresh air introduced into the space. Please provide the CFM as required by the tankless water heater specification.
5. Also, provide the location of the exhaust duct. The exhaust duct shall terminate not less than 3 ft in any direction from any openings in the house (M1502.3).
6. Please provide an electrical load calculation to show that the existing electrical equipment can support the additional load.
7. Please resubmit.
Should you have any questions about these comments, I can be reached sean.severson@tucsonaz.gov.
02/18/2025 PDSD Application Completeness Express REVIEW COMPLETED