Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING v.2
Permit Number - TC-RES-0125-00259
Review Name: RESIDENTIAL NEW DWELLING v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/10/2025 | Site Engineering - Standard | NOT REQUIRED | |||
| 03/06/2025 | Site Zoning - Standard | NOT REQUIRED | |||
| 03/10/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/26/2025 | Residential Building - Standard | REQUIRES RESUBMIT | 1. Smoke alarms are required inside bedrooms and outside each separate sleeping area, R314.3.2 2. Provide a panel schedule showing panel size, circuit numbers, ampacity, wire size and general description, E3404.13 & E3706.2 3. Revise the electrical load calculations following Table E3602.2 for sizing the loads. 4. Show a receptacle outlet within 3’ of each lavatory basin in each bathroom, E3901.6 |
||
| 02/05/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |