Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0125-00020
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/03/2025 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0125-00020 (8742 E PATTERSON DR TUCSON, AZ 85710) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). 1. Verify the Overhead electrical line has the required 22.5 foot clearance from the inside edge of the pool, E4203.6. 2. Tucson Electric Power requires meters and associated equipment to be relocated from under patios when the service is upgraded or the area is enclosed, TEP SR-405.10.L. 3. The service entrance location appears to be located in an enclosed space, please verify location meets TEP and working space requirements. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 01/03/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |