Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0124-00561
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/31/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/31/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0124-00561 (3542 S CHESIN DR TUCSON, AZ 85730) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC). 1. Provide individual appliance demands along with the total demand, G2413.4.1. 2. Size the pipe based on the length from the meter to the farthest attached appliance and max total demand of all attached appliances using Table G2413.4(1) (Metallic Pipe), Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1. 3. The 1β pipe is undersized for the given length (56β) and demand (274K), the minimum size required is 1 ΒΌβ pipe per Table G2413.4(1) (Metallic Pipe). Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 01/31/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |