Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2024 Fire New Construction NOT REQUIRED
02/01/2024 Historic NOT REQUIRED Property is not historically designated and there is no substantial demo of the exterior of the building that triggers historic review.
02/28/2024 Site Engineering NOT REQUIRED
02/28/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/12/2024 Residential Building REQUIRES RESUBMIT TC-RES-0124-00547
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

SECTIONS - DETAILS:

1. Show a complete cross-section detail of the new exterior wall, R106.1.1. Show the minimum 12” x 12” continuous footing, R403.1. Show with dimensions the exterior wood siding and pressure treated sill anchored with ½” x 10” bolts. Show the wall assembly with a 6” clearance above the ground or 2” clearance above an exterior concrete surface, R317.1 item 5.
2. Both standard and high-density R-30 batt insulation requires a space greater than provided with 2” x 6” framing, N1102.1. Identify the products that provide the intended minimum R-30 total value with a 2-layer batt and ridge board system or closed cell foam, R806.5
3. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 or R-30 when extended over the wall top plate for additions under 500 SF.

ELECTRICAL PLANS:

1. Interior alterations require the installation of smoke alarms in existing bedrooms, R314.2.2. Provide notation if the smoke alarms are existing or proposed.
2. Show all receptacle outlets located within 6’ of a sink with ground fault circuit interrupting protection, E3902.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
02/22/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-RES-0124-00547
1113 E ALTA VISTA ST. – R-2
Laundry and Closet Addition (1st Review)

TRANSMITTAL DATE: February 22, 2024

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9, & .10.

1. Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Building-Safety/Plan-Examples/Plot-Plan-Example, to include but not limited to:
a. Provide a lot coverage calculation on the plot plan.
b. Show the location of all utilities on the plot plan.
c. Provide the property dimensions on the plot plan.
d. Provide the legal description, “VISTA HERMOSA HOMESITES LOT 14 EXC N9' FOR ALLEY BLK 9” on the plot plan.
e. Indicate the zoning of this parcel and all adjacent parcels on the plot plan.
f. Provide perimeter yard setback dimensions from the proposed additions to the applicable property lines.

2. Perimeter yard setbacks are based on a wall height measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A. Where the wall meets the eave of the roof. Per UDC Table 6.3-2.A the minimum perimeter yard setback from the proposed addition to the west property line is 6’-0” or 2/3 (H) height of the building exterior wall, great of the two. Based on a wall height of less than 9’-0” the requirement setback from the addition to the west property line is 6’-0”, based on the dimensions shown on sheet A105 the proposed setback is 5’-4”. A Design Development Option (DDO) must be submitted and approved to reduce the required setback. DDO application and requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration. If you have questions about the DDO application or process please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov or Georgia Pennington at Georgia.Pennington@tucsonaz.gov.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.