Permit Number: TC-RES-0124-00538
Parcel: 125151460

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0124-00538
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/30/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
01/30/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0124-00538 (342 N COUNTRY CLUB RD TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Provide a panel schedule showing panel size, circuit numbers, ampacity, wire size and general description of the new 50A circuit, E3404.13 & E3706.2. Provide a panel schedule showing wire size of each new circuit or notate the wire size for each protection rating, E3702.2.

2. Provide a floor plan showing the location of each receptacle and outlet, E3901.2.

3. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3. GFCI protected, E3902.6.

4. Show a receptacle outlet within 3’ of each lavatory basin in each bathroom, E3901.6. Show Bathroom receptacles with a separate 20 AMP dedicated circuit, E3703.4 and E3901.6.

5. Show GFCI protection for Bathroom, laundry room, outdoor, garage receptacles, and receptacles withing 6’ of wet bar sink per E3902.

6. Show Protection of all interior 15A & 20A circuits serving outlet locations (except garage, and bathrooms) including receptacles, lights and smoke detectors with require combination type arc-fault circuit interrupters, E3902.16.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
01/30/2024 PDSD Application Completeness REVIEW COMPLETED