Review Date Reviewer's Name Type of Review Description Status Comments
02/29/2024 Site Engineering NOT REQUIRED
03/15/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/15/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT FROM: Veronica Flores
PDSD Residential Review Section

PROJECT: TC-RES-0124-00431
INSTALLING ROOF MOUNT SOLAR PANELS-(1st Review)
(7502 E Clarence Ci)

TRANSMITTAL DATE: March 15th, 2024

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a Written Response Letter to each of the notated items indicating action taken. Resubmitted plans/calculations that do not contain a written Response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.

COMMENTS: Code reference, 2018 International Residential Code (IRC).

1. After a review of aerial views(https://maps2.tucsonaz.gov/Html5Viewer/?viewer=maptucson#) of the property, it appears that PV modules are mounted on an unpermitted structure on the west side of the building. Searching city records through PRO (https://pro.tucsonaz.gov/address_search/) found no permit history for this structure. Either provide completed permit and inspection documentation, apply for and complete permit review and inspections for the structure or remove the PV modules from the unpermitted structure.

2. For wind uplift use 115 mph in 3sec gust, Table R301.2(1). https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/building-code/2018_-_irc_amendments.pdf

3. Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability, or provide an engineer’s calculation, and sealed design, R301.1, R324.4.

Any questions contact Building_official@tucsonaz.gov