Permit Number: TC-RES-0124-00428
Parcel: 136307490

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0124-00428
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2024 Site Engineering NOT REQUIRED
02/16/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
02/09/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0124-00428 (4700 S FENWICK DR TUCSON, AZ 85730)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. The #8 AWG conductor, between the disconnect and meter collar, is undersized for the given OCPD. Conductors shall be protected with OCPD’s having a rating not exceeding the allowable ampacity of the conductor, IRC E3705.5, reference NEC 310.15, 240.4.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov