Permit Number: TC-RES-0124-00416
Parcel: 114270570

Review Status: Requires Resubmit

Review Details: RESIDENTIAL POOL v.1

Permit Number - TC-RES-0124-00416
Review Name: RESIDENTIAL POOL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2024 Site Zoning NOT REQUIRED
01/30/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/30/2024 Residential Building REQUIRES RESUBMIT ACTIVITY NO. TC-RES-0124-00416
ADDRESS/PARCEL: 3205 N COTTONWOOD CI/114-27-0600


Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

COMMENTS:
1. Show the pool surface area and location in relation to all existing structures on the property, 2018 ISPSC 105.3.
2. Show compliance with the pool enclosure barrier requirement by including a continuous 5 foot barrier around the pool, ARS 36-1681.
3. Show compliance with the pool barrier from a dwelling by including a UL 2017 listed pool alarm system for doors and windows open to the pool, or show a continuous barrier around the pool, 2018 ISPSC 305.4.1.
4. Notate and specify all piping materials and equipment, P2608.
5. Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). Provide a gas line isometric or table for showing the BTU demand and length of line to each gas appliance.
6. Show electrical home run on site plan.
7. Use Table E3705.5.3 for sizing 15, 20 & 30 AMP branch circuit conductors and protection ratings.
8. Use Table E3705.1, 60 degree C column, for sizing branch circuits and conductors rated at 100 AMP or less, E3705.4.1.
9. Bond the perimeter surface and reinforcing steel as required by ISPSC 302.1 and NEC680.26(B)(2).


If you have any questions about these comments, I can be reached at Matthew.Carlton@tucsonaz.gov
01/25/2024 PDSD Application Completeness Express REVIEW COMPLETED