Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-RES-0124-00343
Parcel: 116022520

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.2

Permit Number - TC-RES-0124-00343
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
01/19/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0124-00343 (2786 W CALLE DE DALIAS TUCSON, AZ 85745)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

1. The ¾ inch pipe is undersized for the given demand. Modification to the gas fired appliances and meter, require the submission of a gas pipeline template, G2401.1, R301.1.

2. Provide a complete gas piping template showing the connection from the meter to ALL gas appliances. Include pipe size, type and length. Provide appliance demands. G2413.4.1

3. Size the pipe based on the length from the meter to the farthest attached appliance and max total demand of all attached appliances using Table G2413.4(1) (Metallic Pipe), Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
01/19/2024 PDSD Application Completeness REVIEW COMPLETED