Permit Number: TC-RES-0124-00240
Parcel: 136126400

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.2

Permit Number - TC-RES-0124-00240
Review Name: RESIDENTIAL NEW DWELLING v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2024 Site Engineering NOT REQUIRED
03/18/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
03/06/2024 Residential Building REQUIRES RESUBMIT Permit Review TC-RES-0124-00240 (10066 E LURLENE DR TUCSON, AZ 85730)
2nd Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

General comments:
1. Show a ½” gypsum board (garage side) on all walls common to the garage and house or other fire rated product in compliance with R302.6.
2. Provide a flashing connection detail that shows prevention of water intrusion between the two structures. R703.1.1, R703.4.


Electrical Plans:
1. An attached garage requires a Garage Branch Circuit: a separate (dedicated) GFCI 20-amp branch circuit required for receptacles in an attached garage and detached garages with service, E3703.5.

2. Provide an Electrical Plan, IRC E3401. Construction documents shall indicate the Main Panel and any Sub-Panel locations and shall provide information on wiring methods, circuiting and electrical load calculations which demonstrate that the premises electrical system has load capacity to accommodate the new electrical loads.
3. Provide a panel schedule showing panel size, circuit numbers, ampacity, wire size and general description, IRC E3404.13 & E3706.2. Provide a panel schedule showing wire size of each circuit or notate the wire size for each protection rating, IRC E3702.2.
4. Garage Branch Circuit: a separate (dedicated) GFCI 20-amp branch circuit required for receptacles in an attached garage and detached garages with service, IRC E3703.5.
5. Garage Receptacle Location: a 20 AMP receptacle outlet is required at each vehicle bay not more than 5.5 feet above the floor, IRC E3901.9.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
03/07/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: Wyatt Berger
Lead Planner

PROJECT: TC-RES-0124-00240
10066 East Lurlene Drive – RX-1
Detached garage – (2nd Review)

TRANSMITTAL DATE: March 7, 2024

Please resubmit revised drawings with a detailed response letter stating how all Zoning Review Section comments were addressed.

4. This comment has not yet been addressed. Accessory structures shall not exceed 12 feet in height, unless attached to a principal structure (UDC 6.6.3.D) Per a previous Zoning Administrator's determination, the proposal may be considered attached to the principal structure if a five-foot-wide structural element that can support a minimum twenty pound live load is proposed. A Board of Adjustment variance is required to be granted to allow the proposal to exceed 12 feet in height if the above structural element requirement cannot be met.

If you have any questions about this review, contact me at Wyatt.Berger@tucsonaz.gov or at 520-837-4951.
02/25/2024 PDSD Application Completeness REVIEW COMPLETED