Permit Number: TC-RES-0124-00104
Parcel: 121070830

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0124-00104
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/08/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0124-00104 (1413 N SONOITA AV TUCSON, AZ 85712)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Note and specify all piping materials (Black Iron, Gas line PEX, etc.), G2412.9.
2. Provide max demand for each appliance. Size the pipe based on the length from the meter to the farthest attached appliance and max total demand of all attached appliances using Table G2413.4(1) (Metallic Pipe), Table G2413.4(7) Polyethylene Plastic Pipe. Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1.
3. The 3/4” pipe is undersized for the given demand and length. Provide a minimum size of 1” BIP for this system.
4. The ½” pipe to the furnace is undersized for the given demand and length. Provide a minimum size of ¾” BIP for the furnace branch.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
01/08/2024 PDSD Application Completeness Express REVIEW COMPLETED