Permit Number: TC-RES-0124-00073
Parcel: 123052990

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0124-00073
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/05/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0124-00073 (2210 E JUANITA ST TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Clarify the scope of work by showing the existing Amp rating of the service and show the new Amp rating of the service.
2. Is the service entrance being relocated? Show the location of the existing panel on the Electrical Plan and indicate if it will be a junction point for existing circuits or a sub-panel with new feeder conductors, E3601.6.2 & E3705.8.
3. Provide an electrical riser diagram showing the support structure for the new service entrance, E3403, 3404.8. Notate the grounding and bonding method, E3603.4, E3607. Metallic gas lines must be bonded and not be used as the primary grounding method, E3608.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov