Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/07/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0124-00073 (2210 E JUANITA ST TUCSON, AZ 85719)
2nd Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

>>> The following comments were not addressed. Provide both updated plans and a response letter detailing your solution to each issue below.

1. Provide an electrical riser diagram showing the support structure for the new service entrance, E3403, 3404.8. Notate the grounding and bonding method, E3603.4, E3607. Metallic gas lines must be bonded and not be used as the primary grounding method, E3608.

>>> Additional comments due to significant load addition to the main panel. (New electrical to shed? Workshop?)

2. Provide a grounding electrode on the Riser Diagram for both the Main-panel and the sub-panel, E3607.3.
3. Provide an electrical plan showing the location of all new electrical work and circuits added that require the 400A service. Show the location of each outlet on the Electrical Plan/floorplan, E3404.12.
4. Designate the circuit number at the location of each light fixture, receptacle, appliance, and equipment disconnect switch, E3404.12.
5. Provide a panel schedule showing panel size, circuit numbers, ampacity, wire size and general description, E3404.13 & E3706.2. Provide a panel schedule showing wire size of each circuit or notate the wire size for each protection rating, E3702.2.
6. Show the feeder OCPD and conductor size and type from the main panel to the 200A sub-panel, E3601.6.2, E3704.1, E3705.8.
7. Show GFCI protection for all workshop receptacles per E3902.2, E3902.15.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov