| 02/17/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/17/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit review TC-RES-0123-02442 PLUMBING Plans: 1. Note and specify all piping materials and sizes, P2609. 2. Use G2413.4.1 and G2413.4.2 to determine required developed length. 3. Use Table G2413.4(1) to calculate correct required pipe sizes. 4. The measurements on the provided plans are not clear. For instance, what does the 26’ and 27’ measurements refer to? 5. What are the measurements to the T for the Furnace, the T for the range and the T for the fireplace? 6. Provide updated plans that have measurements to each branch, T, and appliance. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||