Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0123-02442
Parcel: 121063510

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-RES-0123-02442
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/17/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/17/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit review TC-RES-0123-02442

PLUMBING Plans:
1. Note and specify all piping materials and sizes, P2609.
2. Use G2413.4.1 and G2413.4.2 to determine required developed length.
3. Use Table G2413.4(1) to calculate correct required pipe sizes.
4. The measurements on the provided plans are not clear. For instance, what does the 26’ and 27’ measurements refer to?
5. What are the measurements to the T for the Furnace, the T for the range and the T for the fireplace?
6. Provide updated plans that have measurements to each branch, T, and appliance.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
02/03/2023 PDSD Application Completeness Express REVIEW COMPLETED