Permit Number: TC-RES-0123-02435
Parcel: 106022200

Address:
221 W PASTIME RD

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0123-02435
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2023 Site Engineering NOT REQUIRED
02/10/2023 Site Landscape NOT REQUIRED
03/07/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/06/2023 Residential Building REQUIRES RESUBMIT TC-RES-0123-02435

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

Clarify if the renovated structure is a sleeping quarters (without kitchen) or a qualifying Accessory Dwelling Unit (ADU) which requires collection of impact fee.

SITE PLAN:

1. Remove the new electrical meter (sheet S-2) or obtain Zoning approval for a new street address for the dwelling unit, R319.

SECTIONS - DETAILS:

1. Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation or need for providing air-impermeable rigid insulation at the roof, R806.
2. Show an unvented roof assembly with all insulation at the roof including an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing as part of the total insulation requirement, R806.5.
3. Show compliant interior wall insulation, N1102.1.

PLUMBING PLANS:

1. Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). Provide a BTU demand for the proposed gas line to the kitchen area.

ELECTRICAL PLANS:

1. Provide a Riser Diagram showing an underground feeder size from a service panel to the Sleeping Quarters sub-panel, NEC 225.30 and E3403.

OUTDOOR LIGHTING CODE

1. Show the proposed fixtures as full cut-off FCO style or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits.

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
(520) 837-4912 PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/pdsd
03/06/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: Wyatt Berger
Lead Planner

PROJECT: TC-RES-0123-02435
221 W Pastime Rd – R-2
Storage remodel (2nd Review)

TRANSMITTAL DATE: March 6, 2023

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. Remove the reference to a new electrical meter on Sheets S-2 and E-1. Also, demonstrate that the "kitchen" as depicted on Sheet F-1 will not include full cooking facilities to ensure the building is not classified as a third dwelling unit (multifamily development).

If you have any questions about this transmittal, contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov or at 520-837-4951.
02/09/2023 PDSD Application Completeness Express REVIEW COMPLETED