Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0123-02411
Parcel: 116111450

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.2

Permit Number - TC-RES-0123-02411
Review Name: RESIDENTIAL SOLAR v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/07/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0123-02411

• Provide Main Service Panel (MSP) taps in compliance with (NEC 705.12(B)(2)(3) b Busbars.) 120% bus bar rule.
• Plans show a 100A service panel with 26.25A input from PV. 26.25 > max OCPD for 100A bus bar.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
03/06/2023 PDSD Application Completeness Express REVIEW COMPLETED