Permit Number: TC-RES-0123-02335
Parcel: 103192160

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0123-02335
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2023 Site Landscape APPROVED
03/29/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/29/2023 Fire New Construction REQUIRES RESUBMIT Provide either two fire hydrants within 600' (as the hose would lay) of all portions of the structure or provide a fire sprinkler system in accordance with NFPA 13d. Reference IFC 2018, 507.5 and Appendix D. Questions: Patricia Shelton, 520.837.7082, patricia.shelton@tucsonaz.gov
03/27/2023 Residential Building REQUIRES RESUBMIT TC-RES-0123-02335
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL COMMENTS :

1. A special inspection request is required with the updated plans for the post-tensioned slab, R109.2.

PLANS:

1. Provide manufacturer’s calculations and data for pre-engineered trusses dated and wet-sealed by an engineer who is registered in Arizona, or notate the requirement for deferred submittal, R106.1.
2. Show braced wall panel compliance for (narrow) framed walls with a garage door opening, Table R602.10.5. For prescriptive braced wall structures show a portal frame with hold-downs PFH method, Figure R602.10.6.2, or a portal frame at garage door PFG method, Figure R602.10.6.3, or a continuously sheathed portal frame CS-PF method, Figure R602.10.6.4.

SECTIONS - DETAILS:

1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38. Update keynote #3/A6.0; #12/S4.0 & #2/S4.1.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
(520) 837-4912 PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/pdsd
03/24/2023 Site Engineering REQUIRES RESUBMIT Engineering cannot approve until TD-DEV-0123-00107 has been issued
03/21/2023 Site Zoning REQUIRES RESUBMIT Until TD-DEV-0123-00107 Zoning cannot approve this plan.
02/28/2023 PDSD Application Completeness Express REVIEW COMPLETED