Permit Number: TC-RES-0123-02319
Parcel: 128140520

Address:
5202 E 17TH ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0123-02319
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2023 Site Engineering NOT REQUIRED
02/08/2023 Site Landscape NOT REQUIRED
02/17/2023 Site Zoning NOT REQUIRED
03/06/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/06/2023 Residential Building REQUIRES RESUBMIT Permit Review TC-RES-0123-02319
PLAN REVIEW COMMENTS
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and https://www.tucsonaz.gov/files/integrated-planning/pdsd/2018_-_IRC_Amendments.PDF. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.
Floor Plans:
1. Label all rooms and spaces. Show floor plan for all rooms adjoining bathroom. R106.1.1.
2. Specify nonabsorbent wall surface minimum 6’ above the floor with cement, fiber-cement, or glass-mat board backing in tub/shower enclosures, R307.2, R702.4.2.
3. Specify wall and ceiling covering. Note: Ceiling gypsum board must be either 5/8” or ½” sag resistant when applied to ceilings framed at 24” o/c, IRC Table R702.3.5 footnote d.
Plumbing plans:
1. Specify water conservation requirements: P2903.6.
2. Note and specify all piping materials, both waste and potable (hot/cold) lines, P2609.
3. Plumbing vents shall be a minimum of 10 feet away from all air intakes, P3103.5.
Mechanical Plans:
1. Show exhaust fan locations for bathroom venting to the exterior (min 50 CFM), R303.3, M1505.
Electrical Plans:
1. Bathrooms require a separate dedicated 20-amp circuit with receptacles within 3’ of the basins, E3703.4, E3901.6.
2. GFCI protection is required in bathrooms, E3902.
3. Lights installed over shower or bathtub must be approved for use in wet areas, E4003.9.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
02/07/2023 PDSD Application Completeness Express REVIEW COMPLETED