Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - TC-RES-0123-02130
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/22/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/22/2023 | Residential Building | REQUIRES RESUBMIT | Permit Review TC-RES-0123-02130 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and https://www.tucsonaz.gov/files/integrated-planning/pdsd/2018_-_IRC_Amendments.PDF. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes. See https://www.tucsonaz.gov/pdsd/residential-permits for example plans. Structures built without a permit may require alteration for building code compliance. SITE PLAN: 1. Indicate the location and size of buildings, utility meters (gas, electrical, water) and lines (gas, electrical, water, sewer), R106.1.1. ELECTRICAL Plan: 1. Provide carbon monoxide alarms per R315. Alarms must be installed in residences with attached garages and/or fuel fired appliances when any work is performed that requires a permit. 2. Smoke detectors are required in existing buildings when interior alterations occur, R314.2.1. 3. Show location of the panel with a 30”Wx36”D clear working space, E3405.2, E3405.4. 4. Provide riser diagrams for MSP and sub-panels with feeder conductors, conduit sizes and over-current protection E3705.3. 5. Provide a panel schedule: panel size, circuit number, ampacity and wire sizes OCPD, E3404.11, E3706.2. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 02/17/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |