Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-0123-01996
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/11/2023 | Site Engineering | NOT REQUIRED | |||
| 09/28/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/28/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | TC-RES-0123-01996 Resubmit comment: Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). 1. OCPD for copper conductor may not exceed 15A for #14, 20A for #12 or 30A for #10 rating required by NEC 240.4(D)(small conductors). See sheet E1.1 Wire Tag #3. |
||
| 09/08/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |