Permit Number: TC-RES-0123-01973
Parcel: 132112170

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0123-01973
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2023 Light Residential Building Review (OIP) APPROVED
01/26/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/19/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-RES-0123-01973

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
NEED THE RACKING INSTALLATION INSTRUCTIONS INCLUDING THE SPANS AND THE GROUNDING/BONDING DETAILS AND DIAGRAM.
THE PROPERTY SHOWN ON THE IMAGES ON THE COVER PAGE ARE FOR A DIFFERENT PROPERTY.


BUILDING REVIEW COMMENTS:
Denied
NEED THE RACKING INSTALLATION INSTRUCTIONS INCLUDING THE SPANS AND THE GROUNDING/BONDING DETAILS AND DIAGRAM.
THE ROOF PLAN VIEW AREA IS 1400 SF AND THE AREA COVERED BY THE ARRAY EXCEEDS 33% WHICH REQUIRES A MINIMUM OF 36" SETBACK AT EACH SIDE OF THE RIDGE PER SECTION R324.6.2 - SHOW THE ROOF ACCESS POINTS MEETING THE REQIREMENTS OF SECTION R324.6
THE PROPERTY SHOWN ON THE IMAGES ON THE COVER PAGE ARE FOR A DIFFERENT PROPERTY.


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
Denied
NEED THE RACKING INSTALLATION INSTRUCTIONS INCLUDING THE SPANS AND THE GROUNDING/BONDING DETAILS AND DIAGRAM.
THE ROOF PLAN VIEW AREA IS 1400 SF AND THE AREA COVERED BY THE ARRAY EXCEEDS 33% WHICH REQUIRES A MINIMUM OF 36" SETBACK AT EACH SIDE OF THE RIDGE PER SECTION R324.6.2 - SHOW THE ROOF ACCESS POINTS MEETING THE REQIREMENTS OF SECTION R324.6
THE PROPERTY SHOWN ON THE IMAGES ON THE COVER PAGE ARE FOR A DIFFERENT PROPERTY.
THE INCORRECT AMBIENT TEMPERATURE CORRECTION FACTOR WAS USED IN THE CALCULATIONS. SEE SECTION R310.15.


PLUMBING REVIEW COMMENTS:
N/A


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
01/09/2023 PDSD Application Completeness Express REVIEW COMPLETED