Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-RES-0123-01900
Parcel: 117061560

Address:
123 N JACOBUS AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.2

Permit Number - TC-RES-0123-01900
Review Name: RESIDENTIAL NEW DWELLING v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
03/07/2023 Residential Building REQUIRES RESUBMIT REV-2

1. Provide a Service Panel Schedule showing bus amp rating and all branch-circuits. E3706.1, E3706.2.
a. Show addition of new branch-circuit loads for WH and Dryer in the schedule.
2. Show Service Panel meets requirements in E3706.3 – E3706.5.
a. Provided plans do not include Panel bus bar rating. Main braker indicates 100A which may be too small for additional loads.
3. To verify MSP bus can handle the new continuous loads, provide a load calculation table as prescribed by E3704 and Table E3704.2(1).
4. Provide a wiring size schedule showing all new work complies with E3701.2, E3705. Use Table E3705.1 90 degree C column for type and sizes for new loads.
a. Provided plans do not show wire type or size being used for two new circuits (WH and Dryer).
5. Provided Spec Sheet for Rheem RETEX-13 shows a continuous current rating of 54A and suggested OCPD of 60A. Electrical plans show addition of a 40A OCPD.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov