Permit Number: TC-RES-0123-01883
Parcel: 126061740

Address:
4050 E 3RD ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0123-01883
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2023 Site Engineering NOT REQUIRED
01/10/2023 Site Landscape NOT REQUIRED
02/06/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/06/2023 Residential Building REQUIRES RESUBMIT 1. Show the building setback to property line, R106.1.1.
2. A roof overhang may not extend closer than 24” to the neighboring property line. Any part of a roof projection extending into the 3-foot fire separation distance from the property line requires not less than one-hour fire-resistive construction on the underside, R302.1 (City of Tucson Amended).
01/24/2023 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: TC-RES-0123-01883
4050 E 3RD ST Zoning R-1

TRANSMITTAL DATE:‎January 24, 2023


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1.COMMENT: Zoning is unable to write DDO comment please provide the setback dimension to the new addition on the west property line. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A). Based on a calculated wall height of 9’-3” the required perimeter yard setback from the proposed addition to the west property line is 6’-3”, A Design Development Option (DDO) may be required to reduce the required setback,
DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. If you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov.


2.COMMENT Perimeter yard setbacks are based on a measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A. Provide a dimension form design grade to where the wall hits the eave and the peak of the roof for the west elevation so that setback requirements can be verified.

3.COMMENT: On the south portion of the lot there is a 5ft wide utility easement.




If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
01/24/2023 Zoning Modifications - DDO REQUIRES RESUBMIT A Design Development Option (DDO) must be submitted and approved to reduce the required setback. The DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/2019_DDO_for_Setback_and_Height_UDC.pdf.

Please contact me at Georgia.Pennington@tucsonaz.gov or at 520-837-6311 should you have questions about this transmittal.
01/06/2023 PDSD Application Completeness Express REVIEW COMPLETED