Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-0123-01874
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/06/2023 | Site Engineering | NOT REQUIRED | |||
| 02/06/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/23/2023 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Activity Number: TC-RES-0123-01874 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: CONDITIONALLY APPROVED Solar panel mounting and anchorage to be as described in the licensed engineer’s structural analysis. Staggered mounting required. Maximum horizontal roof mount spacing no greater than 48 inches on center. Maximum vertical roof mount spacing no greater than 3.292 ft on center. Minimum (2) 5/16 inch diameter lag screws with a minimum 2-1/2 inch embedment required at each connection. Hold for Electrical approval BUILDING REVIEW COMMENTS: CONDITIONALLY APPROVED Expansion of existing system. Roof penetrations shall be flashed in accordance with IRC R324.4.3 Hold for Electrical approval MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS DENIED Show new and existing disconnect switches on the line diagrams. PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
||
| 01/31/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Activity Number TC-RES-0123-01874: Provide OCPD calculations for New and Existing PV sources. Provide OCPD calculations for combined PV source to MSP. Provide MSP calculations showing the system meets the 120% bus bar rule. |
||
| 01/17/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |