Permit Number: TC-RES-0123-01844
Parcel: 116161560

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0123-01844
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/06/2023 Site Landscape APPROVED
03/23/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/17/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-RES-0123-01844
1008 N Contzen Ave - R-3
New SFR w/Sleeping Quarters (1st Review)

TRANSMITTAL: March 17, 2023

Provided a detail comment response letter with your submittal that clearly shows how you have addressed all comments with your next submittal.

This site is located in the R-3 zone (UDC 4.7.10). A single-family residence (SFR) with sleeping quarters is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6.

1. Per UDC Article 6.6.3.C. Detached accessory buildings, including accessory dwelling units, are not permitted in the buildable area extending the full width of the lot between the principal building and the front street lot line, except for terraces and steps not over three feet high above the natural grade, paved areas, and fences or walls. As the proposed SFR does not meet the minimum 20’-0” street perimeter yard setback to Delong St. Zoning considers Contzen Ave as the front street. That said the sleeping quarters is considered an accessory structure and is not allowed in the front yard. A Board of Adjustment for Variance will be required to permit the plans as shown.

2. Perimeter yard setbacks are based on a measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A. As a dimension was not provided from design grade to the highest point of the wall Zoning cannot verify perimeter yard setback requirements.

3. Provide perimeter yard setback dimensions from the post supporting the proposed porches to the applicable property lines. These structures are required to meet perimeter yard setbacks.

4. It does not appear that the lot coverage calculation is not correct. Review UDC Article 6.4.3 and the example shown on the Residential Plot Plan Requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf, and provide a correct lot coverage calculation.

5. There is a carport shown on the west end to the propose SFR on the plot plan but this carport is not shown on the floor plan or elevations.

If you have questions about the Board of Adjustment please contact Mark Castro at Mark.Castro@tucsonaz.gov.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov
03/14/2023 Fire New Construction REVIEW COMPLETED
03/06/2023 PDSD Application Completeness Express REVIEW COMPLETED
03/23/2023 Residential Building REVIEW COMPLETED