Permit Number: TC-MDP-1225-00797
Parcel: 120073630

Address:
3820 S LUNDY AV

Review Status: Requires Resubmit

Review Details: SITE FROM MODEL TEMPLATE - INFILL BUILDERS v.1

Permit Number - TC-MDP-1225-00797
Review Name: SITE FROM MODEL TEMPLATE - INFILL BUILDERS v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/31/2025 Residential Building APPROVED
01/02/2026 Fire New Construction NOT REQUIRED
01/13/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/26/2025 Residential Engineering REQUIRES RESUBMIT Permit: TC-MDP-1225-00797
Location: 3820 S LUNDY AV
Review Date: 12/26/2025
Site Engineering Comments:
1. Provide more detail regarding the new fence along the property boundaries. This would include proposed height and material type.
If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
01/02/2026 Residential Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Roxanne Johnston
Planner

PROJECT: TC-RES-1225-00797
3820 S Lundy Av.,, Tucson, AZ 85714 (1st Review)

TRANSMITTAL DATE: 01/02/2026

This site is located within the R-2 Zone (UDC 4.7.9). A duplex is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.6, .9, & .10.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Correct plans, as noted in the comments below, along with a response letter indicating how all Site Zoning comments were addressed.

1. The proposed duplex square footage does not match the approved model under TC-MDP-1025-00706. Unit 1 of the approved model duplex contains 1071 sq, ft. Unit #2 contains 848 sq. ft.. The unstamped model labeled “Charly” contains the matching square footage and was a draft as it was submitted before the stamped plan was issued. Please submit a plan that matches the approved stamped plans.

2. Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted for the next review.

If you have any questions about this transmittal, please contact Roxanne Johnston at roxanne.johnston@tucsonaz.gov .
12/29/2025 ROW Engineering Review REQUIRES RESUBMIT Site plan: Show existing and proposed Right-of-Way features. Provide distances and dimensions for the following:
1. Driveway (PAG SD 206) Max. width for residential driveway is 20’
2.Sidewalk (PAG SD 200) 5’ for arterial roadways.
3.Road Type: Local
*Unused existing curb cuts shall be closed.
12/24/2025 PDSD Application Completeness Express REVIEW COMPLETED
01/13/2026 TW New Development Review Fast REVIEW COMPLETED