Permit Number: TC-MDP-1225-00769
Parcel: 116180460

Review Status: Requires Resubmit

Review Details: SITE FROM MODEL TEMPLATE INFILL BUILDERS REVISION v.1

Permit Number - TC-MDP-1225-00769
Review Name: SITE FROM MODEL TEMPLATE INFILL BUILDERS REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/24/2026 Residential Engineering APPROVED
03/25/2026 Fire New Construction NOT REQUIRED
04/16/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/31/2026 Residential Building REQUIRES RESUBMIT A wall with 3-foot separation distance to the property line may include windows.  A building with less than 3-foot separation requires a fire rated wall without windows. Change the setback or provide revised plans with appropriate fire rating.
04/03/2026 Residential Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Erick Bieber
Planning & Development Services Department – Zoning Review Section

PROJECT: TC-MDP-1225-00769
232 N Melrose Ave Unit 2, Tucson, AZ 85745
Residential Model Permit Revision (1st Review)

TRANSMITTAL DATE: April 3rd, 2026

This site is located in the R-2 zone (UDC 4.7.9). An accessory dwelling unit is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.6, 8 & 9 and 6.6.3.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Correct plans, as noted in the comments below, along with a response letter indicating how all Site Zoning comments were addressed.

1. (Comment) The minimum perimeter yard setback in the R-2 zone is 5’. The proposed ADU is indicated as having a setback of 2’, with email correspondence later clarifying the intention to adjust the setback to 3’. A Design Development Option (DDO) will be required.

Please submit a DDO application under the Zoning Modification sub-record that has been created. For instructions on how to apply for a sub-record, visit the following link: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/sub-records_071425.pdf
For additional questions regarding DDOs, contact Mark Castro at Mark.Castro@tucsonaz.gov.

2. (Comment) Please adjust the position of the proposed ADU on the site plan to reflect the desired setback for the DDO application and the next submittal.


The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code

For questions regarding Zoning comments, please contact me at: Erick.Bieber@tucsonaz.gov
03/24/2026 PDSD Application Completeness Express REVIEW COMPLETED
04/16/2026 ROW Engineering Review REVIEW COMPLETED