Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-MDP-1224-01365
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/13/2025 | Commercial Building | APPROVED | |||
| 01/13/2025 | Site Engineering | APPROVED | |||
| 01/09/2025 | Site Zoning | APPROVED | |||
| 01/13/2025 | Commercial Mechanical | NOT REQUIRED | |||
| 01/13/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/09/2025 | Commercial Electrical | REQUIRES RESUBMIT | Commercial Electrical Review: TC-MDP-1224-01365 (544 E LIMBERLOST DR Unit:BLDG 1 TUCSON, AZ 85705) TC-MDP-1224-01371 (544 E LIMBERLOST DR Unit:BLDG 3 TUCSON, AZ 85705) TC-MDP-1224-01388 (544 E LIMBERLOST DR Unit:BLDG 2 TUCSON, AZ 85705) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Show power utility distribution from TEP source to each building/unit. Show location of panel boards, transformers and Underground power utility lines. 2. Specify overhead or underground electrical service. Overhead service for new construction requires an appeal to the Building Official, IBC amendment section 112.1.1. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 01/13/2025 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Provide a design for the water service to the building, including pipe material, pipe sizes, and valves. Reference: Section 107.2.1, IBC 2018. 2. Provide a design to show how the building sewer is connected to the private sewer collection system. Show the pipe material, pipe size, cleanouts, and backwater valves. Reference: Section 107.2.1, IBC 2018. 3. The use of saddle-type fittings to connect to a private sewer is prohibited. Use directional wye fittings to connect the building sewers to the sewer main. Reference: Section 707.1 (6), IPC 2018. |
||
| 01/10/2025 | Outdoor Lighting | REQUIRES RESUBMIT | Outdoor Lighting Review TC-MDP-1224-01365 (544 E LIMBERLOST DR Unit:BLDG 1 TUCSON, AZ 85705) TC-MDP-1224-01371 (544 E LIMBERLOST DR Unit:BLDG 3 TUCSON, AZ 85705) TC-MDP-1224-01388 (544 E LIMBERLOST DR Unit:BLDG 2 TUCSON, AZ 85705) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). Outdoor Lighting Code (OLC). 1. Provide an outdoor lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your table and use the same number on your site plan 2. Provide a Special Inspection Certificate as required by OLC 106.2. 3. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. Show lamps with a maximum of 3500K color temperature, OLC 402.1. 4. Show compliance to total outdoor light output per 2012 City of Tucson/Pima County Outdoor Lighting Code section 401.2. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. 4. E1.1 – Lighting Code section 104.2.2. 5. Submit catalogue or specification sheets of the proposed light fixture illustrating the type of fixture they are whether full cut-off or unshielded. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 01/13/2025 | Water - PDSD | REQUIRES RESUBMIT | Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018. | ||
| 12/19/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 12/19/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |