Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-MDP-1123-01794
Parcel: 141430170

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - TC-MDP-1123-01794
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
03/14/2024 Post-Tension Inspection (Deferred Submittal) REQUIRES RESUBMIT ACTIVITY NO. TC-MDP-1123-01794
ADDRESS/PARCEL: (6843 E PASEO DE VILLALOBOS TUCSON, AZ 85756)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
COMMENTS:
1. Post Tension Concrete specification strength within structural drawings is 3,000 psi, four locations are below 3,000 psi (as low as 2,467 psi). Please have Project Structural Engineer review and obtain his recommendation (should he/she decides to approve this report, a seal/signature/date will be required on the Hammer Test result report along with his statement for accepting the test result).
2. Please resubmit.
03/11/2024 PDSD Application Completeness REVIEW COMPLETED
03/14/2024 Post-Installed Anchor Inspection (Deferred Submittal) REVIEW COMPLETED
03/14/2024 Site Prep Inspection (Deferred Submittal) REVIEW COMPLETED SOIL COMPACTION