Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-MDP-1024-01214
Parcel: 12912083A

Address:
1715 S PARK AV

Review Status: Requires Resubmit

Review Details: SITE FROM MODEL TEMPLATE - INFILL BUILDERS v.1

Permit Number - TC-MDP-1024-01214
Review Name: SITE FROM MODEL TEMPLATE - INFILL BUILDERS v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/17/2025 Fire New Construction NOT REQUIRED
04/21/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/16/2025 Residential Building REQUIRES RESUBMIT Show the location of sewer HCS on the site plan. Coordinate with Pima County Wastewater, R106.1.1. https://www.pima.gov/1766/Wastewater-Reclamation
04/17/2025 ROW Engineering Review REQUIRES RESUBMIT NOTE :
1) Call out Future Right of Way Limits for Park Ave and 27th St
2) Call out - Existing and Future Driveways locations
3) *Unused existing curb cuts shall be closed

Provide distances and dimensions for the following:
Driveway (PAG SD 206) Max. width for residential driveway is 20’
2.Sidewalk (PAG SD 200) 5' for arterial roadways.
4.For property access off collector/arterial roadways, show onsite vehicle maneuverability.
04/21/2025 Site Engineering REQUIRES RESUBMIT TC-MDP-1024-01214
1715 S PARK AV

Site engineering comments are as follows:
1. Engineering cannot approve this Model Permit until all reviewers’ comments have been addressed and corrected on the site plan.
2. Please show driveways, future right-of-way, and correct lot coverage calculation.
Ryan Insalaco – ryan.insalaco@tucsonaz.gov
04/18/2025 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-MDP-1024-01214
1 715 S PARK AV. – C-2
New Duplex (1st Review)

TRANSMITTAL DATE: April 18, 2025

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-2 zone (UDC 4.7.21). A duplex is a permitted use in this zone (Table 4.8-4).

1. The lot coverage calculation is not correct. Review UDC Article 6.4.3 and the example shown on the Residential Plot Plan Requirements found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Building-Safety/Plan-Examples/Plot-Plan-Example, and provide a correct lot coverage calculation. Clarify which of the two options you are going to use and provide a correct lot coverage calculation.

2. As Park Ave. is designated as a Arterial on the COT MS&R Map, found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Development-Tools-Resources/Plans#section-5, with a future width of 120’ or 60’ ½ right-of-way (ROW) and the existing Park Ave. is not a full future width, show the future ROW line, future curb and sidewalk on the plan. Review the MS&R plan found at the above link for future ROW requirements.

3. The Park Ave. street perimeter yard setback shown on the plan, 10’-0” is not correct. Per UDC Article 6.4.5.C.1.a is 20’measured from the future ROW line.

4. Revise the sheet index to only include the sheet submitted.

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
04/04/2025 PDSD Application Completeness Express REVIEW COMPLETED added condition for addressing