Permit Review Detail
Review Status: Requires Resubmit
Review Details: SITE FROM MODEL TEMPLATE - INFILL BUILDERS v.1
Permit Number - TC-MDP-0824-00978
Review Name: SITE FROM MODEL TEMPLATE - INFILL BUILDERS v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/08/2024 | Site Zoning | APPROVED | |||
| 09/26/2024 | Fire New Construction | NOT REQUIRED | |||
| 09/26/2024 | ROW Engineering Review | NOT REQUIRED | Shown work is within Property and outside ROW | ||
| 10/11/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/04/2024 | Residential Building | REQUIRES RESUBMIT | Permit Review TC-MDP-0824-00978 (3114 N ALVERNON WY Unit:UNIT 5 TUCSON, AZ 85712) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). The Development package shows units 4 and 5 with only 4’ of separation. TD-DEV-0224-00033. Fire separation: The line used to determine fire separation distance is an imaginary line drawn between the two structures. 1. Any structure placed within the 3-foot fire separation distance, from the line used to determine the fire separation distance, requires not less than one-hour fire-resistive construction for reducing fire spread across the line, R302.1(City of Tucson Amended). Fire rated materials are found in IBC Table 721.1(2), Items 15-1.1 to 16-1.3. No windows, doors or vents are allowed in the fire rated wall assembly. 2. Roof projections extending into the 3-foot fire separation distance require not less than one-hour fire-resistive construction on the underside, R302.1 (City of Tucson Amended). The fire protected overhang may not extend closer than 24” from the line used to determine the fire separation distance. The minimum distance between structures, with no fire rated wall assembly, is 6’ and a maximum 1’ overhang. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 10/11/2024 | Site Engineering | REQUIRES RESUBMIT | Site engineering comments are as follows: 1. Because this development is in a floodplain, it will require a Floodplain Use Permit with Elevation Certificate before this permit can be approved. Ryan Insalaco Engineering Associate City of Tucson Planning & Development Services Department Email: ryan.insalaco@tucsonaz.gov Phone: (520) 837-5351 |
||
| 09/26/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |