Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - TC-MDP-0823-01426
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2025 Site Prep Inspection (Deferred Submittal) Express APPROVED
01/31/2025 Truss Design (Deferred Submittal) Express APPROVED
02/03/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/03/2025 Post-Installed Anchor Inspection (Deferred Submittal) Express REQUIRES RESUBMIT ACTIVITY NO. TC-MDP-0823-01426

ADDRESS/PARCEL: (615 W ALTURAS ST Unit:BLDG 13 TUCSON, AZ 85705)

Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter.

COMMENTS:

1 - PE letter regarding post-installed anchors does not cover the specified unit. Must provide letter for lot 13.

2 - Post-Tensioning results inspection shows lot 7 on page one and lot 13 on page 2. Please provide results for all of lot 13 and remove lot 7.

3 - Please resubmit.

Should you have any questions about these comments, I can be reached at ian.gillaspie@tucsonaz.gov.
01/31/2025 Post-Tension Inspection (Deferred Submittal) Express REQUIRES RESUBMIT ACTIVITY NO. TC-MDP-0823-01426

ADDRESS/PARCEL: (615 W ALTURAS ST Unit:BLDG 13 TUCSON, AZ 85705)

Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter.

COMMENTS:

1 - PE letter regarding post-installed anchors does not cover the specified unit. Must provide letter for lot 13.

2 - Post-Tensioning results inspection shows lot 7 on page one and lot 13 on page 2. Please provide results for all of lot 13 and remove lot 7.

3 - Please resubmit.

Should you have any questions about these comments, I can be reached at ian.gillaspie@tucsonaz.gov.
01/29/2025 PDSD Application Completeness Express REVIEW COMPLETED