Permit Review Detail
Review Status: Requires Resubmit
Review Details: SITE FROM MODEL TEMPLATE - INFILL BUILDERS v.2
Permit Number - TC-MDP-0726-00584
Review Name: SITE FROM MODEL TEMPLATE - INFILL BUILDERS v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/17/2026 | Residential Zoning | APPROVED | |||
| 08/27/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/17/2026 | Fire New Construction | REQUIRES RESUBMIT | *Per 2024 IFC Appendix D, Table D103.4. Fire apparatus access roadways need to be a minimum unobstructed width of 20 feet with an unobstructed height of 15 feet (2024 IFC 503.2.1). *Per 2024 IFC Appendix D, D104.3 states: Dead-end fire apparatus access roads in excess of 150 feet shall be provided with width and turn-around provisions in accordance with Table D103.4 and Figure D103.1. *Fire truck access to this structure cannot be accomplished as shown in the plan drawing. |
||
| 08/27/2026 | Residential Engineering | REQUIRES RESUBMIT | Reviewer: John Mounsey – Engineering Associate - Residential Engineering Reviewer Contact: John.mounsey@tucsonaz.gov Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed to ensure final approval from Site Engineering. Submit your response letter and updated plan set as two separate files. Residential Engineering Review Comments: 1. Residential Engineering has completed its review of the submitted building plan. However, final approval cannot be granted until the comments addressed by Fire Review have been addressed and plans are resubmitted. |
||
| 08/13/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |