Permit Number: TC-MDP-0625-00375
Parcel: 136171860

Review Status: Requires Resubmit

Review Details: SITE FROM MODEL TEMPLATE - INFILL BUILDERS v.1

Permit Number - TC-MDP-0625-00375
Review Name: SITE FROM MODEL TEMPLATE - INFILL BUILDERS v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2025 Residential Building APPROVED
07/02/2025 Fire New Construction NOT REQUIRED
07/18/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/18/2025 Site Engineering REQUIRES RESUBMIT Permit: TC-MDP-0625-00375
Location: 3362 S STEARN LAKE DR
Review Date: 7/18/2025
Site Engineering Comments:
1. There is a 1ft no access easement that is located along the east portion of the property along Camino seco that is shown per Lakecrest No.4 final plat.

If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
07/11/2025 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-MDP-0625-00375
3362 S STEARN LAKE DR. – R-1
New SFR (1st Review)

TRANSMITTAL DATE: July 11, 2025

COMMENTS: Provide a detailed response letter with your submittal that clearly shows how you have addressed all Zoning comments.

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

1. Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Plan-Examples/Plot-Plan-Example, to include but not limited to:
a. Provide a lot coverage calculation that meets the requirements of UDC Article 6.4.3 and the example shown on the Residential Plot Plan Requirements. This calculation shall provided a breakdown of building sf and vehicle use area whether improved or unimproved.
b. Provide a dimension from the centerline of Stearn Lake Rd. to the face of curb, where pavement meets the concrete curb, and from face of curb to north property line. Per Construction Plan I-72-059, sheet 9, found at: https://maps-and-records.tucsonaz.gov/construction-plans/details/I-72-059, the distance from centerline to face of curb is 15’ and from face of curb to the north property line is 10’.
c. Per the Lakecrest No.4 final plat, found at: https://maps-and-records.tucsonaz.gov/subdivisions/details/2754, there is a 1’-0” No Access Easement that runs along the east property line. Show this easement on the plan and label it.

2. The drawing index provided on the plan is not correct.

3. Until demo permit, TC-DMO-0625-00130, is approved by all review agencies Zoning cannot approve this permit.

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
06/27/2025 PDSD Application Completeness Express REVIEW COMPLETED
06/27/2025 ROW Engineering Review REVIEW COMPLETED Separate permit submission will be required for Work to be performed within City ROW for each scope of work.